Schedule 1 Parameters

 

Units

PCV

Number of Samples

Number of Samples contravening PCV

% No. of samples contravening PCV

Min

Mean

Max

Colour

mg/l Pt/Co

20

26

0

0

<1.70

1.81

3.00

Turbidity

FTU

4

26

0

0

0.10

0.13

0.54

Odour (quantitative)

Dil Number

0

26

0

0

0

0

0

Taste (quantitative)

Dil Number

0

26

0

0

0

0

0

Sodium

mg/l

200

10

0

0

16.60

19.13

21.70

Nitrate (as NO3)

mg/l

50

10

0

0

12.40

22.19

31.20

Nitrite (as NO2)

mg/l

0.1

10

0

0

<0.01

<0.01

0.01

Nitrate/Nitrite Ratio

mg/l

1

10

0

0

0.25

0.44

0.62

Aluminium

ug/l

200

26

0

0

6.00

10.02

15.40

Iron

ug/l

200

26

0

0

5.30

13.89

159.00

Manganese

ug/l

50

26

0

0

1.70

1.89

6.70

Copper (New Reg Limit)

mg/l

2

10

0

0

0.01

0.03

0.10

Fluoride

mg/l

1.5

10

0

0

<0.11

0.78

1.08

Arsenic (New Regs Limit)

ug/l

10

10

0

0

1.00

1.05

1.20

Cadmium

ug/l

5

10

0

0

0.12

0.12

0.12

Chromium

ug/l

50

10

0

0

<0.70

<0.70

<0.70

Nickel (New Reg Limit)

ug/l

20

10

0

0

<0.80

1.25

3.50

Lead (New Reg Limit)

ug/l

10

10

0

0

<0.90

0.90

0.90

Antimony (New Reg Limit)

ug/l

5

10

0

0

0.20

0.39

0.60

Selenium

ug/l

10

10

0

0

0.80

0.80

0.80

PAH

ug/l

0.1

10

0

0

0

0

0

Escherichia coli

No./100ml

0

78

0

0

0

0

0

Intestinal Enterococci

cfu/100ml

0

10

0

0

0

0

0

Boron (New Reg Limit)

mg/l

1

10

0

0

0.04

0.06

0.08

Benzo(a)pyrene

ug/l

0.01

10

0

0

<0.003

<0.003

<0.003

Trihalomethanes (total)

ug/l

100

8

0

0

5.57

39.27

65.90

Bromate

ug/l

10

10

0

0

0.80

0.81

0.90



Indicator parameters

 

Units

PCV

Number of samples

Number of Samples contravening PCV

% No. of samples contravening PCV

Minimum

Mean

Maximum

pH (New Reg Limit) Env

 

-

26

0

0

7.00

7.32

7.80

Sulphate (as SO4)

mg/l

250

10

0

0

54.80

63.41

67.80

Ammonium (as NH4)

mg/l

0.5

26

0

0

<0.03

<0.03

<0.03

Total coliforms

No./100ml

0

78

0

0

0

0

0

3 day count,22 deg C

cfu/ml

50

26

0

0

0

1

6

Free chlorine

mg/l

-

78

0

0

0.06

0.30

0.63

Total chlorine

mg/l

-

78

0

0

0.17

0.48

0.84

Conductivity

uS/cm

2500

26

0

0

458.00

557.85

675.00

Chloride

mg/l

250

10

0

0

50.00

67.00

92.00


*All of the samples collected from this zone in 2022 complied with the Water Supply (Water Quality) (Amendment) Regulations 2016.  Supplies to this zone are fluoridated up to a level of 1.5mg/l


Water hardness
Average of Ca Average of Mg mg/l or ppm CaCO3 Degrees Clark (*0.07) Degrees French (*0.10) Degrees German (*0.056)
82.32 10.25 247.7 17.3 24.8 13.9


Water quality terms